1 | AN ACT concerning regulation.
| |||||||||||||||||||
2 | Be it enacted by the People of the State of Illinois,
| |||||||||||||||||||
3 | represented in the General Assembly:
| |||||||||||||||||||
4 | Section 5. The Illinois Plumbing License Law is amended by | |||||||||||||||||||
5 | adding Section 35.5 as follows: | |||||||||||||||||||
6 | (225 ILCS 320/35.5 new) | |||||||||||||||||||
7 | Sec. 35.5. Reclaimed water recycling systems; exemption | |||||||||||||||||||
8 | for governmental units. | |||||||||||||||||||
9 | (a) For purposes of this Act, "reclaimed water" means a | |||||||||||||||||||
10 | combination of harvested storm (raw) water, domestic potable | |||||||||||||||||||
11 | water, and condensated water from air conditioning systems. | |||||||||||||||||||
12 | (b) If a unit of local government regulates reclaimed water | |||||||||||||||||||
13 | systems, then those reclaimed water systems must meet the | |||||||||||||||||||
14 | requirements of this Section. | |||||||||||||||||||
15 | (c) Reclaimed water systems must meet all of the following | |||||||||||||||||||
16 | requirements: | |||||||||||||||||||
17 | (1) All reclaimed water recycling systems must comply | |||||||||||||||||||
18 | with the provisions of the Illinois Plumbing Code, 77 Ill. | |||||||||||||||||||
19 | Adm. Code 890. | |||||||||||||||||||
20 | (2) Above-ground drain, waste, and vent piping for | |||||||||||||||||||
21 | reclaimed water systems must conform to accepted standards | |||||||||||||||||||
22 | listed in Table A of Appendix A of 77 Ill. Adm. Code 890. | |||||||||||||||||||
23 | Reclaimed water, underground building drainage, and vent |
| |||||||
| |||||||
1 | pipe must conform to one of the standards listed in Table A | ||||||
2 | of Appendix A of 77 Ill. Adm. Code 890. | ||||||
3 | (3) The drain, waste, and vent piping for any reclaimed | ||||||
4 | water system must be tested in accordance with 77 Ill. Adm. | ||||||
5 | Code 890.1910. | ||||||
6 | (4) All reclaimed water systems must be inspected in | ||||||
7 | accordance with 77 Ill. Adm. Code 890.1910. | ||||||
8 | (5) Only connections in accordance with this Section | ||||||
9 | may be made between a reclaimed water system and a potable | ||||||
10 | water system. | ||||||
11 | (6) Reclaimed water systems must receive only the water | ||||||
12 | discharge of gutters, downspouts, roof drains, AC | ||||||
13 | condensate drains, and potable water system. | ||||||
14 | (7) Reclaimed water must be collected in a reservoir | ||||||
15 | constructed of durable, nonabsorbent, and | ||||||
16 | corrosion-resistant materials. The reservoir must be a | ||||||
17 | closed and vented vessel. Access openings must be provided | ||||||
18 | to allow inspection and cleaning of the reservoir interior. | ||||||
19 | (8) Harvested rain water entering the reservoir must | ||||||
20 | pass through an approved filter, such as a media, or mesh | ||||||
21 | screen. | ||||||
22 | (9) An air gap must be installed downstream of the | ||||||
23 | potable water fill line connection to the collection | ||||||
24 | reservoir. | ||||||
25 | (10) The collection reservoir must be equipped with an | ||||||
26 | overflow pipe having the same or larger diameter as the |
| |||||||
| |||||||
1 | influent pipe for the harvested storm water. The overflow | ||||||
2 | pipe must be indirectly connected to drainage swale or | ||||||
3 | storm sewer. | ||||||
4 | (11) The reservoir must be provided with a vent sized | ||||||
5 | in accordance with Department requirements and based on the | ||||||
6 | diameter of the reservoir influent pipe. | ||||||
7 | (d) Systems for flushing water closets and urinals must | ||||||
8 | meet all of the following requirements: | ||||||
9 | (1) The holding capacity of the reservoir must be a | ||||||
10 | minimum of twice the volume of water required to meet the | ||||||
11 | daily flushing requirements of the fixtures supplied with | ||||||
12 | reclaimed water, but not less than 50 gallons (189 Liters). | ||||||
13 | (2) Reclaimed water must be disinfected by a method | ||||||
14 | approved by the Department that employs one or more | ||||||
15 | disinfectants such as chlorine, iodine, or ozone. | ||||||
16 | (3) Potable water must be supplied as a source of | ||||||
17 | makeup water for the reclaimed water system. The potable | ||||||
18 | water supply must be protected against backflow in | ||||||
19 | accordance with 77 Ill. Adm. Code 890.1110. | ||||||
20 | (4) The reclaimed water must be dyed blue or green with | ||||||
21 | a food grade vegetable dye before such water is supplied to | ||||||
22 | the fixtures. | ||||||
23 | (5) Distribution piping must conform to one of the | ||||||
24 | standards listed in Table A of Appendix A of 77 Ill. Adm. | ||||||
25 | Code 890. | ||||||
26 | (6) Distribution piping and reservoirs must be |
| |||||||
| |||||||
1 | identified as containing non-potable water. Distribution | ||||||
2 | fittings to be identified with signs. Piping | ||||||
3 | identification must be in accordance with 77 Ill. Adm. Code | ||||||
4 | 890.1120. | ||||||
5 | (e) Surface landscape irrigation systems must meet all of | ||||||
6 | the following requirements: | ||||||
7 | (1) Reservoirs must be sized to maintain a 2-day supply | ||||||
8 | of irrigation water. | ||||||
9 | (2) The reservoir must be identified as containing | ||||||
10 | non-potable water. | ||||||
11 | (3) A check valve and a full-open valve located on the | ||||||
12 | discharge side of the check valve must be installed on the | ||||||
13 | effluent pipe of the collections reservoir. | ||||||
14 | (4) Makeup water is not required for surface landscape | ||||||
15 | irrigation systems. Where makeup water is provided, the | ||||||
16 | installation must be in accordance with paragraph (3) of | ||||||
17 | subsection (d) of this Section. | ||||||
18 | (5) Disinfection is not required for reclaimed water | ||||||
19 | used for surface landscape irrigation systems. | ||||||
20 | (6) Reclaimed water used for surface landscape | ||||||
21 | irrigation systems is not required to be dyed. | ||||||
22 | (7) The system must be sized in accordance with | ||||||
23 | standards set by the Department. | ||||||
24 | (f) Nothing in this Act prohibits the State or any | ||||||
25 | governmental unit from installing and using a reclaimed water | ||||||
26 | recycling system, including systems for flushing of water |
| |||||||
| |||||||
1 | closets and urinals and surface landscape irrigation systems. | ||||||
2 | However, any reclaimed water recycling system must be in | ||||||
3 | accordance with the requirements of this Section.
| ||||||
4 | Section 99. Effective date. This Act takes effect upon | ||||||
5 | becoming law.
|