| "Section 5. The Fire Sprinkler Contractor Licensing Act is |
5 |
| amended by changing Section 30 as follows:
|
6 |
| (225 ILCS 317/30)
|
7 |
| Sec. 30. Requirements for the installation and repair of |
8 |
| fire protection
systems. |
9 |
| (a) Equipment shall be listed by a nationally recognized |
10 |
| testing laboratory,
such as
Underwriters Laboratories, Inc. or |
11 |
| Factory Mutual Laboratories, Inc., or shall
comply with |
12 |
| nationally
accepted standards. The State Fire Marshal shall |
13 |
| adopt by rule procedures for
determining
whether a laboratory |
14 |
| is
nationally recognized, taking into account the laboratory's |
15 |
| facilities,
procedures, use of nationally
recognized |
16 |
| standards, and any other criteria reasonably calculated to |
17 |
| reach an
informed
determination.
|
18 |
| (b) Equipment shall be installed in accordance with the |
19 |
| applicable standards
of the National
Fire Protection |
20 |
| Association and the manufacturer's specifications.
|
21 |
| (c) The contractor shall furnish the user with operating |
22 |
| instructions for
all equipment
installed, together with a |
23 |
| diagram of the final installation.
|
24 |
| (d) All fire sprinkler systems shall have a backflow |