| ||||
Public Act 096-1292 | ||||
| ||||
| ||||
AN ACT concerning safety.
| ||||
Be it enacted by the People of the State of Illinois,
| ||||
represented in the General Assembly:
| ||||
Section 5. The Facilities Requiring Smoke Detectors Act is | ||||
amended by changing Section 2 as follows:
| ||||
(425 ILCS 10/2) (from Ch. 127 1/2, par. 822)
| ||||
Sec. 2.
(a) Every facility shall be equipped with at least | ||||
one
approved smoke detector in an operating condition within 15 | ||||
feet of every room
used for sleeping purposes. The detector | ||||
shall be installed on the ceiling
and at least 6 inches from | ||||
any wall, or on a wall located between 4 and 6
inches from the | ||||
ceiling.
| ||||
(b) Every facility shall have at least one approved smoke | ||||
detector installed on
every story of the facility, including | ||||
basements but not including
unoccupied attics; provided that | ||||
there shall be at least one detector at
the beginning and at | ||||
the end of each separate corridor or hallway 200 feet
or more | ||||
in length in any occupied story, including basements.
| ||||
(c) Every facility shall have at least
one
approved smoke | ||||
detector at the uppermost ceiling of
each interior stairwell, | ||||
except in fire resistive structures. The detector
shall be | ||||
installed on the ceiling,
at least 6 inches from the wall, or | ||||
on a wall located between 4 and 6
inches from the ceiling.
|
(d) The requirements of this Section shall apply to any | ||
facility
in existence on July 1, 1988, beginning on that date. | ||
Except as provided
in subsection (e), the smoke
detectors | ||
required in such facilities may be either battery powered or
| ||
wired into the structure's AC power line, and need not be | ||
interconnected.
| ||
(e) In the case of any facility unit that is newly | ||
constructed,
reconstructed or substantially remodelled after | ||
December 31, 1987, the
requirements of this Section shall apply | ||
beginning on the first day of
occupancy of the facility after | ||
such construction, reconstruction or
substantial remodelling. | ||
The smoke detectors required in such facility
shall be | ||
permanently wired into the structure's AC power line and, if
| ||
more than one detector is required to be installed within the | ||
facility,
the detectors shall be wired so that the actuation of | ||
one detector will
actuate all the detectors in the facility | ||
unit. | ||
In the case of any facility unit that is newly constructed,
| ||
reconstructed, or substantially remodeled on or after January | ||
1, 2011, smoke detectors permanently wired into the structure's | ||
AC power line must also maintain an alternative back-up power | ||
source, which may be either a battery or batteries or an | ||
emergency generator.
| ||
(f) Compliance with an applicable federal, State or local | ||
law, rule or
building code which requires the installation and | ||
maintenance of smoke
detectors in a manner different from this |
Section, but providing a level of
safety for occupants which is | ||
equal to or greater than that provided by
this Section, shall | ||
be deemed to be compliance with this Section, and the | ||
requirements of
such more stringent law shall govern over the | ||
requirements of this Section.
| ||
(g) In
the case of a
facility subject to this Act, the | ||
provisions of this Act shall be enforced
by the State agency | ||
which licenses that facility.
The State licensing agency may | ||
suspend the
facility's license for a violation of this Act | ||
where appropriate.
| ||
(Source: P.A. 85-936.)
| ||
Section 10. The Smoke Detector Act is amended by changing | ||
Section 3 as follows:
| ||
(425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
| ||
Sec. 3.
(a) Every dwelling unit shall be equipped with at | ||
least one
approved smoke detector in an operating condition | ||
within 15 feet of every room
used for sleeping purposes. The | ||
detector shall be installed on the ceiling
and at least 6 | ||
inches from any wall, or on a wall located between 4 and 6
| ||
inches from the ceiling.
| ||
(b) Every single family residence shall have at least one | ||
approved smoke
detector installed on every story of the | ||
dwelling unit, including basements
but not including | ||
unoccupied attics. In dwelling units with split levels,
a smoke |
detector installed on the upper level shall suffice for the
| ||
adjacent lower level if the lower level is less than one full | ||
story below
the upper level; however, if there is an | ||
intervening door between the
adjacent levels, a smoke detector | ||
shall be installed on each level.
| ||
(c) Every structure which (1) contains more than one | ||
dwelling unit, or
(2) contains at least one dwelling unit and | ||
is a mixed-use structure, shall
contain at least one approved | ||
smoke detector at the uppermost ceiling of
each interior | ||
stairwell. The detector shall be installed on the ceiling,
at | ||
least 6 inches from the wall, or on a wall located between 4 | ||
and 6
inches from the ceiling.
| ||
(d) It shall be the responsibility of the owner of a | ||
structure to supply
and install all required detectors. The | ||
owner shall be responsible for
making reasonable efforts to | ||
test and maintain detectors in common
stairwells and hallways. | ||
It shall be the responsibility of a tenant to
test and to | ||
provide general maintenance for the detectors within the
| ||
tenant's dwelling unit or rooming unit, and to notify the owner | ||
or the
authorized agent of the owner in writing of any | ||
deficiencies which the
tenant cannot correct. The owner shall | ||
be responsible for providing one
tenant per dwelling unit with | ||
written information regarding detector
testing and | ||
maintenance.
| ||
The tenant shall be responsible for replacement of any | ||
required batteries
in the smoke detectors in the tenant's |
dwelling unit, except that the owner
shall ensure that such | ||
batteries are in operating condition at the time
the tenant | ||
takes possession of the dwelling unit. The tenant shall provide
| ||
the owner or the authorized agent of the owner with access to | ||
the dwelling
unit to correct any deficiencies in the smoke | ||
detector which have been
reported in writing to the owner or | ||
the authorized agent of the owner.
| ||
(e) The requirements of this Section shall apply to any | ||
dwelling unit
in existence on July 1, 1988, beginning on that | ||
date. Except as provided
in subsections (f) and (g), the smoke | ||
detectors required in such dwelling
units may be either battery | ||
powered or wired into the structure's AC power
line, and need | ||
not be interconnected.
| ||
(f) In the case of any dwelling unit that is newly | ||
constructed,
reconstructed, or substantially remodelled after | ||
December 31, 1987, the
requirements of this Section shall apply | ||
beginning on the first day of
occupancy of the dwelling unit | ||
after such construction, reconstruction or
substantial | ||
remodelling. The smoke detectors required in such dwelling
unit | ||
shall be permanently wired into the structure's AC power line, | ||
and if
more than one detector is required to be installed | ||
within the dwelling
unit, the detectors shall be wired so that | ||
the actuation of one detector
will actuate all the detectors in | ||
the dwelling unit.
| ||
In the case of any dwelling unit that is newly constructed,
| ||
reconstructed, or substantially remodeled on or after January |
1, 2011, smoke detectors permanently wired into the structure's | ||
AC power line must also maintain an alternative back-up power | ||
source, which may be either a battery or batteries or an | ||
emergency generator. | ||
(g) Every hotel shall be equipped with operational portable
| ||
smoke-detecting alarm devices for the deaf and hearing impaired | ||
of audible
and visual design, available for units of occupancy.
| ||
Specialized smoke-detectors for the deaf and hearing | ||
impaired shall be
available upon request by guests in such | ||
hotels at a rate
of at least one such smoke detector per 75 | ||
occupancy units or portions
thereof, not to exceed 5 such smoke | ||
detectors per hotel.
Incorporation or connection into an | ||
existing interior alarm system, so as
to be capable of being | ||
activated by the system, may be utilized in lieu of
the | ||
portable alarms.
| ||
Operators of any hotel shall post conspicuously at the main | ||
desk a
permanent notice, in letters at least 3 inches in | ||
height, stating that
smoke detector alarm devices for the deaf | ||
and hearing impaired are
available. The proprietor may require | ||
a refundable deposit for a portable
smoke detector not to | ||
exceed the cost of the detector.
| ||
(h) Compliance with an applicable federal, State or local | ||
law or
building code which requires the installation and | ||
maintenance of smoke
detectors in a manner different from this | ||
Section, but providing a level of
safety for occupants which is | ||
equal to or greater than that provided by
this Section, shall |
be deemed to be in compliance with this Section, and
the | ||
requirements of such more stringent law shall govern over the
| ||
requirements of this Section.
| ||
(Source: P.A. 85-1404.)
| ||
Section 99. Effective date. This Act takes effect January | ||
1, 2011.
|