TITLE 77: PUBLIC HEALTH
CHAPTER I: DEPARTMENT OF PUBLIC HEALTH SUBCHAPTER r: WATER AND SEWAGE
PART 890
ILLINOIS PLUMBING CODE
SECTION 890.APPENDIX A PLUMBING MATERIALS, EQUIPMENT, USE RESTRICTIONS AND APPLICABLE STANDARDS
Section 890.APPENDIX A
Plumbing Materials, Equipment, Use Restrictions and Applicable Standards
Section 890.TABLE O Water
Supply Fixture Units (WSFU) for a Supply System with Flushometer Water
Closets
|
|
WSFU
|
Demand (GPM)
|
Pipe Size (Inches)
|
Pressure Loss (PSI/100'
of Pipe)
|
Velocity (Ft./Sec.)
|
Meter Size (Inches)
|
|
|
|
|
|
|
10
|
27
|
1¼"
|
8.3
|
6.8
|
¾"
|
12
|
28.6
|
1¼"
|
9.2
|
7.2
|
¾"
|
14
|
30.2
|
1¼"
|
10
|
7.9
|
¾"
|
16
|
31.8
|
1¼"
|
11
|
8.0
|
¾"
|
20
|
35
|
1½"
|
6.0
|
6.4
|
¾"
|
25
|
38
|
1½"
|
7.0
|
6.9
|
1"
|
30
|
41
|
1½"
|
8.0
|
7.4
|
1"
|
35
|
43.8
|
1½"
|
8.8
|
8.0
|
1"
|
40
|
46.5
|
2"
|
2.5
|
4.7
|
1"
|
45
|
49
|
2"
|
2.7
|
5.1
|
1"
|
50
|
51.5
|
2"
|
2.9
|
5.4
|
1½"
|
60
|
55
|
2"
|
3.4
|
5.8
|
1½"
|
70
|
58.5
|
2"
|
3.7
|
6.0
|
1½"
|
80
|
62
|
2"
|
4.0
|
6.2
|
1½"
|
90
|
64.8
|
2"
|
4.6
|
6.5
|
1½"
|
100
|
67.5
|
2"
|
5.0
|
6.8
|
1½"
|
120
|
72.5
|
2"
|
5.6
|
7.2
|
2"
|
140
|
77.5
|
2"
|
6.3
|
8.0
|
2"
|
160
|
82.5
|
2½"
|
2.7
|
5.7
|
2"
|
180
|
87
|
2½"
|
3.0
|
6.1
|
2"
|
200
|
91.5
|
2½"
|
3.4
|
6.4
|
2"
|
225
|
97
|
2½"
|
3.7
|
6.8
|
2"
|
250
|
101
|
2½"
|
4.0
|
7.1
|
3"
|
275
|
106
|
2½"
|
4.2
|
7.3
|
3"
|
300
|
110
|
2½"
|
4.6
|
7.6
|
3"
|
350
|
119
|
3"
|
2.1
|
5.5
|
3"
|
400
|
126
|
3"
|
2.3
|
5.9
|
3"
|
450
|
138
|
3"
|
2.7
|
6.3
|
3"
|
500
|
145
|
3"
|
3.0
|
6.8
|
3"
|
600
|
160
|
3"
|
3.6
|
7.4
|
4"
|
750
|
178
|
4"
|
1.1
|
4.7
|
4"
|
1000
|
208
|
4"
|
1.5
|
5.6
|
4"
|
1250
|
240
|
4"
|
1.9
|
6.4
|
4"
|
1500
|
267
|
4"
|
2.3
|
7.0
|
4"
|
1750
|
294
|
4"
|
2.8
|
7.8
|
4"
|
2000
|
321
|
6"
|
0.4
|
3.7
|
6"
|
|
Agency Notes:
|
|
Where a
unit of local government or the community public water supply does not
require separate water service lines for irrigation or similar systems that
are likely to impose continuous demands (e.g., lawn sprinkler or air
conditioning systems), the following rule applies: estimate the continuous
demand (in gallons per minute) for outlets/systems separately from the
intermittent demand from the above fixtures, and add this amount to the
demand of the fixtures (in gallons per minute).
|
|
Meter and
meter yoke sizes shown in this table shall apply only to those jurisdictions
or governmental units where local ordinances or community public water supply
requirements do not prescribe specific sizes of meters or meter yokes. Where
local ordinances or community public water supply requirements cover such
sizing, those requirements shall be followed.
|
(Source: Amended at 38 Ill.
Reg. 9940, effective April 24, 2014)
|