TITLE 77: PUBLIC HEALTH
CHAPTER I: DEPARTMENT OF PUBLIC HEALTH SUBCHAPTER b: HOSPITALS AND AMBULATORY CARE FACILITIES
PART 250
HOSPITAL LICENSING REQUIREMENTS
SECTION 250.TABLE E PIPING LOCATIONS FOR OXYGEN, VACUUM AND MEDICAL COMPRESSED AIR
Section 250.TABLE E Piping
Locations for Oxygen, Vacuum and Medical Compressed Air
Location
|
Oxygen
|
Vacuum
|
Compressed Air
|
Patient Room for Adult
Medical/Surgical Care
|
A
|
A
|
|
Patient Room for Postpartum
Care & Pediatrics
|
A
|
F
|
|
Examination and Treatment
Rooms for Nursing Unit
|
D
|
D
|
|
Patient Room for Intensive
Care
|
C
|
C
|
B
|
Normal Newborn Nursery
|
A
|
B
|
A
|
Special Care & Observation
Nursery
|
B
|
B
|
A
|
General Operating Room
|
E
|
E
|
E
|
Cystoscopy and Special
Procedure Room
|
D
|
D
|
D
|
Recovery Room for Surgical and
Obstetrical Patients
|
B
|
B
|
A
|
Delivery Room
|
E
|
E
|
|
Labor Room
|
A
|
A
|
|
Treatment Room for Emergency
Care
|
D
|
D
|
|
Autopsy Room
|
–
|
D
|
|
Anesthesia Workroom
|
–
|
D
|
|
A
|
=
|
One outlet
accessible to each bed
One outlet
may serve 2 beds
|
|
|
|
B
|
=
|
One outlet
for each bed
|
|
|
|
C
|
=
|
Two
outlets for each bed
|
|
|
|
D
|
=
|
One outlet
|
|
|
|
E
|
=
|
Two
outlets
|
|
|
|
F
|
=
|
One outlet
provided if required by the narrative
|
|