TITLE 41: FIRE PROTECTION
CHAPTER I: OFFICE OF THE STATE FIRE MARSHAL PART 160 STORAGE, TRANSPORTATION, SALE AND USE OF GASOLINE AND VOLATILE OILS: RULES AND REGULATIONS\ RELATING TO GENERAL STORAGE SECTION 160.220 DIKES CAPACITY
Section 160.220 Dikes – Capacity
Dikes surrounding tanks containing crude oil or other flammable liquid subject to boil-over, shall have a capacity of not less than the capacity of the tank surrounded and in addition shall have a coping or deflector pointing inward, so designed and constructed as to minimize the effect of the boil-over wave. The dike shall be not less than 50 feet from the shell of the tank surrounded.
(Source: Amended at 9 Ill. Reg. 10012, effective October 1, 1985) |