TITLE 35: ENVIRONMENTAL PROTECTION
SUBTITLE F: PUBLIC WATER SUPPLIES
CHAPTER I: POLLUTION CONTROL BOARD
PART 604 DESIGN, OPERATION AND MAINTENANCE CRITERIA
SECTION 604.1315 VENTS


 

Section 604.1315  Vents

 

a)         Finished water storage structures must be vented as follows:

 

1)         the overflow pipe must not be considered a vent; and

 

2)         open construction between the sidewall and roof is not permissible.

 

b)         Vents must:

 

1)         prevent the entrance of surface water and rainwater;

 

2)         exclude birds and animals;

 

3)         exclude insects and dust to the extent practicable;

 

4)         on ground level structures, open downward with the opening at least 24 inches above the roof or sod and be covered with 24 mesh non-corrodible screen; and

 

5)         on elevated tanks and standpipes:

 

A)        open downward; and

 

B)        be fitted with either four mesh non-corrodible screen, or with finer mesh non-corrodible screen in combination with an automatically resetting pressure-vacuum relief mechanism, as required by the Agency.